• Flow.Temperature.Pressure.Level.Pumps

  • Measurement.Repair.Environmental.Calibration

  • UKAS.NADCAP.Traceable.Certification

 

DP & Flow Transmitter

Can we help?
MICRO-BAR DIFFERENTIAL PRESSURE/FLOW TRANSMITTER

Micro-Bar electronic transmitter incorporates a capacitance based differential pressure cell for sensitive measurement on Air or other dry gases. Designed for gas flow measurement applications on extraction or ventilation systems, the micro based electronics uses calibration formulae required for Flo- Bar Averaging Pitot tubes, Orifice Plates or other standard DP based sensors. Simply installed adjacent to the flow line, standard pressure impulse tubing links the sensor directly to the Micro-Bar unit. Flow rate, flow units and alarm status are displayed on the two line LCD: external signal transmission is via the 4-20mA loop power,with separate alarm relay and totaliser pulse.

With simple adjustment over a 5:1 full scale pressure range available to the operator on site, the Micro-Bar suits varying process conditions or output scaling requirements. The micro based electronics simplifies site setup procedures, allowing adjustment of alarm output set points, totalisation pulse rate, averaging time and zero checking.

Micro-Bar is applicable to measuring pressure differentials on operating theatres, clean rooms or glove boxes, to monitor system performance and provide alarms. On process monitoring, Micro-Bar is used for air filter blockage monitoring and burner control on furnaces. For these duties, the display shows the pressure drop directly.

FEATURES
  • DP measurement for gases
  • High sensitivity and linearisation for Pitot tube flow measurement
  • Digital flowrate display in Engineering units
  • ±0.5% accuracy
  • Flow totaliser pulse output
  • High and low flow alarms
  • Site programmable outputs

Full Product Specification

Media Air or dry non-corrosive gases
Range (max DP)

See Coding Breakdown for Details
0-30 Pa (0-0.1” wg)
0-100 Pa (0-0.4” wg)
0-150 Pa (0-0.6” wg)
0-300 Pa (0-1.2” wg)
0-1000 Pa (0-4” wg)
0-3000 Pa (0-12” wg)
0-10 kPa (0-40” wg)
0-30 kPa (0-120” wg)
0-1 bar (0-400” wg)
Output 4-20mA
20mA Adjustment 20% to 100% of max DP
Zero DP Setting Adjustable 0-100% of max DP range
Output vs DP Selectable linear or square root
Display 2 line, 16 x 5mm high digits showing flow/pressure, units and alarm status
Power Supply 10-50vdc loop powered
Averaging 0-60 seconds adjustable
Accuracy@20mA ±0.5% of max DP range
±0.75% of reading
Temperature Range 0-40ºC
Long Term Drift 0.5% per year
Static Pressure Max 5 times max DP range
Pressure Connections Pushfit sockets for 4mm OD tubing or 1/4” NPT Female
Alarm Outputs 2 x volt free relay contacts
Selectable NO/NC
Max 1 Amp rating 110V ac/dc
Flow Totaliser One alarm relay optionally selectable as totaliser. 
Max pulse rate 100 pulse/minute.
Pulse length 50msec
Enclosure Polyester. IP66 with separate terminal compartment
Electrical Connections 2 x M20 glands

Recommended Products





loading...

Major Credit Cards Accepted
Call us+44 (0)870 22 00 724 Email ussales@roxspur.com