Roxspur Measurement and Control: For Good Measure RM&C LtdPlaton, Brearley, CT, Nulectrohms, SensitPhone 0870 22 00 724 or email sales@roxspur.com

The flowcomputer Model 0126 has been developed for the calculation of corrected gas volume. It is suitable for almost any type of input signal for flow, temperature and pressure. The corrected flow information will be displayed as well as transmitted with the 4-20mA output signal. All process data and settings can be read and modified through the RS232 or RS485 Modbus communication link.

A liquid version is also available.

Specification
Measured variablesMeasures uncorrected volumetric flow, temperature and pressure in a gas line.
Calculated variablesCalculates the corrected volumetric gas flow using the formula for ideal gas. The reference conditions for temperature and pressure can be defined in the function as well as a compressibility factor. With DP-measurement the uncorrected volume is also calculated from the differential pressure taking into account temperature and pressure compensation.
Input variablesFlow, temperature and pressure.
Output variablesCorrected volumetric flow, temperature and pressure. Resetable and non-resetable totalisers for corrected volume.
DisplayType High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs.
CasingDie-cast aluminium IP67 / NEMA 4 with 2-component UV-resistant coating.
Operating temperature-30°C to +80°C
Power Supply12-24V AC/DC Powered+ output supply to sensors
Data protectionEEPROM backup of all setting. Backup running totals every minute. Data retention at least 10 years. Configuration settings can be password protected.
INPUTS
Flowmeter - pulse inputCoil/sine wave (minimum 20mVpp or 80mVpp - sensitivity selectable), NPN/PNP, open collector, reed-switch, Namur, active pulse signals 8 - 12 and 24V
Flowmeter - analog input(0)4-20mA - with signal calibration feature. Resolution: 14 bit.
Pressure - analog input(0)4-20mA - with signal calibration feature. Resolution: 14 bit.
Temperature - analog input(0)4-20mA - with signal calibration feature. Resolution: 14 bit.
Analog output4-20mA - passive output, galvanically isolated
Flow EquationsGas: Standard Gas volume correction.
Liquid: standard correction for coefficient of volumetric expansion
Available Models
Input TypeModelCode
Pulse0126-P (gas)DIS0107
Analog0126-A (gas)DIS0108
Pulse0126-P (liquid)DIS0109
Analog0126-A (liquid)DIS0110