Roxspur Measurement and Control: For Good Measure RM&C LtdPlaton, Brearley, CT, Nulectrohms, SensitPhone 0870 22 00 724 or email sales@roxspur.com

The DM400 is a loop powered indicator designed to be connected in series with a 4-20mA current loop and to display digitally, in engineering units, the process variable represented by the current flowing. Coarse and fine potentiometers are provided for both SPAN and ZERO adjustment. The DM400 3 ½ digit LCD display requires only 1 volt from the loop. Sealed to IP67, the housing can be mounted, on a probe assembly or wall. The DM401 is a lower cost version of the DM400 requiring 3 volts from the loop and the DM400X is an IS approved version for use in zone 0, 1 or 2 hazardous areas, (EEx ia IIC T5).

Specification
Input4-20mA, two wire (reverse, polarity protected)
Min. Operating CurrentDM400: 3.8mA
DM400X: 3.8mA
DM401: 3.8mA
Max. Loop drop @ 20mADM400: 1.0 Volts
DM400X: 1.6 Volts
DM401: 3.0 Volts
Display3 ½ Digit LCD
Display Range-1000 to +1999 counts 3 1/2 digit
Offset-1000 to +1000 counts at 4mA
Span200 to 2000 counts(16mA change)
Decimal Point3 positions, plus blank
Accuracy± 0.1% rdg, ±1 count
Ambientto 50°C operating
Case Size85mm dia x 114mm overall
EntryM16 & M20
Standard units availableTemperature: °C, °F, °K, %RH
Pressure: bar, bar g, bar abs, mbar, in wg, ft wg, mwg, mmHg, kg/cm², psi, psig, psi abs,
Flow: l/s, l/min, l/h, gal/min, gal/h,
Other: %, m, ft, %CO², ft/min, V dc, mV dc, A dc, mA dc. ft³/min