Products > Indicators & Displays > Totalises And Batchers > Field Mounting Rate Totaliser
The FW Series of digital indicators is specially designed for computing and displaying total and instantaneous flow rates in liquid or gas applications. Versions are available for either pulse or analogue inputs, and a Batch controller is available for pulse inputs. Housed within a rugged, powder-coated aluminium enclosure that is suitable for direct mounting to a flowmeter, pipe, wall or panel. Units are also available mounted directly to the Turbine Liquid Flowmeters. Consult Sales for details. Units are available for pressure and level display, consult sales.
|  |
| Specification |
| Programming | Via keypad |
| Display | Large 40 x 90mm LCD with 7 x 17mm digits & 11 x 8mm digits. Flow - up to 7 digits, Total - 7 digits, Accum. Total - 11 digits. |
| Data Protection | 10 year data retention minimum (total stored at 10min. intervals) |
| INPUT | |
| Pulse | Sine wave, NPN/PNP open collector, reed-switch or NAMUR 0 to 10kHz (selectable de-bounce for low frequencies) |
| Analogue | 0/4 to 20mA or 0 to 10VDC with linear or square-root functions. |
| OUTPUTS | |
| Pulse | Open collector output, scaleable pulse per unit, 20Hz max, 50VDC, 300mA max, 25 or 100msec pulse width. |
| Analogue | Passive 4 to 20mA |
| Power Supply | 7 year lithium battery (4 to 20mA loop or 5 to 24VDC, if required) |
| Housing | UV resistant powder-coated aluminium casing, St.Steel bolts, Polycarbonate window, EPDM, and PE seals. |
| Temperature | -15 to 60ºC |
| Protection | IP67 (IP65 when panel mounted) |
| Dimensions | 130 x 114 x 58mm |
| Panel Cut-Out | 115 x 96mm (L x H) |
| Cable Entry | 1 x M20 and 2 x Pg9 cable glands |
| BATCHER | |
| Outputs | Two open collector outputs for one/two stage control 50VDC, 300mA max |
| Overrun Correction | Automatic |
| Remote Input | One input for Start/Stop batch. |
| ALARM UNIT | |
| Outputs | 2 x open collector outputs programmable as high/low alarms or pulse output 50VDC, 300mA max. |
| OPTIONS | Remote Input: Reset of Total quantity or Batch Total.
Relays/Supply: 12 to 24VAC/DC or 80 to 240VAC supply
Relays: 250VAC/1A max.
Sensor supply: 8.1 to 24VDC, 80mA max. @24V.
Serial Comms RS232/RS485
|
| Available Models |
| Description | Code |
| Analogue input | DIS0090 |
| Pulse input with High/Low alarms | DIS0091 |
| Pulse input with 15-point linearisation | DIS0092 |
| Dual pulse input (no outputs) | DIS0093 |
| Dual pulse input with ratio function | DIS0094 |
| Dual pulse input with A-B or A+B functions | DIS0095 |
| Pulse input Batch Controller | DIS0096 |
|