Roxspur Measurement and Control: For Good Measure RM&C LtdPlaton, Brearley, CT, Nulectrohms, SensitPhone 0870 22 00 724 or email sales@roxspur.com

The New PLATON Fire Sprinkler Flowmeter has been awarded approval from the Loss Prevention Certification Board. The new design allows connection to LPCB approved Victaulic® fittings giving lower installation costs. Uniquely, the metering section can be serviced without isolating the installation from the supply.

This direct-reading flowmeter is ideal for use in automatic sprinkler installations, water spray or deluge systems. Both the traditional Flange Wafer and Victaulic groove designs are approved for regular monitoring and testing of such systems by the LPCB, Loss Prevention Certification Board, under their ‘Rules for Automatic Sprinkler Installations’ in the UK and by equivalent international organisations.

Features:

  • LPCB approved
  • Lower installation costs
  • Simpler to maintain
  • Rugged, well-proven design
  • Vertical or horizontal installation
  • Flow rates from 150-12,500dm 3 /min
  • UK Manufactured and Supported
  • First for price and deliver
Specification
Filter Unit316SS filter inside TPX tube
ConnectionsSuitable for LPCB approved Victaulic fittings
ValvesBrass nickel plated ball valves
TubeBorosilicate glass, l00mm scale
FloatStainless steel
Accuracy±5% of specified test flows
PipingPlated Copper impulse pipe with plated Brass connections
HousingRotatable polyester coated diecast
O Ring SealsNitrile rubber
Pressure Test30 Bar hydraulic
CertificationLPCB
Test Results
Flow Range (dm3/min)Nominal BoreFlanged Wafer CodeVictaulic® Groove CodeTest Flow (dm3/min)Accuracy (dm3/min)
150-75050F1/5F1/10500±25
300-150080F1/6F1/11800±40
300-150080F1/6F1/111300±65
500-2500100F1/7F1/121500±75
500-2500100F1/7F1/122200±110
1000-5000150F1/8F1/132500±125
1000-5000150F1/8F1/133500±175
1000-5000150F1/8F1/134500±225
2500-12500200F1/9F1/145000±250
2500-12500200F1/9F1/147000±350
2500-12500200F1/9F1/149000±450