Products > Pressure > DP Transmitters > Digital Pressure Gague
The Micro-bar range are two-wire loop powered 4 to 20mA transmitters based on a built-in capacitance based differential pressure cell for low range measurement on air and other dry gases. Standard pressure connections are push-fit sockets but units are also available with ¼"NPTF threads. The Liquid Crystal Display shows the measured pressure and status of the alarm outputs. Alternatively, when used in conjunction with Orifice plates, Pitots or other DP based flow sensors, units can be configured to provide root extraction of the pressure measurement, to display flow rate. Two switch outputs are programmable as flow or pressure setpoints or, for flow measurement, to provide a totaliser output pulse. |  |
| Specification |
| Media | Air and non-corrosive dry gases |
| Process Connections | 2 x pushfit connectors for 4mm OD tubing (1/4"NPTF available to special order) |
| Static Pressure | For DP ranges £1000Pa: 30kPa max For DP ranges >1000Pa: 10bar max Over Range: 5 times DP range max |
| Electrical Connections | 2 x M20 cable glands |
| Temperature | 0 to 40ºC |
| Outputs | Current 4 to 20mA loop powered |
| Switches | Two volt-free solid-state relays (NO/NC) 110V AC/DC, 1 Amp max |
| Loop Supply | 10 to 50VDC |
| Loop Resistance | 700W max. @ 24V |
| Output Range | Adjustable 20% to 100% of model DP range |
| Functions | Linear or square root |
| Display | 2 line x 16 character LCD |
| Accuracy | ±0.5% of max DP |
| Protection | IP66 |
| Available Models |
| Pressure Range | Code |
| 0-30 Pa (0.1" WG) | MB0-DR-01-ST |
| 0-100 Pa (0.4" WG) | MB1-DR-01-ST |
| 0-150 Pa (0.6" WG) | MB1A-DR-01-ST |
| 0-300 Pa (1.2" WG) | MB2-DR-01-ST |
| 0-1000 Pa (4" WG) | MB3-DR-01-ST |
| 0-3000 Pa (12" WG) | MB4-DR-01-ST |
| 0-10 KPa (40" WG) | MB5-DR-01-ST |
| 0-30 KPa (120" WG) | MB6-DR-01-ST |
| 0-1 Bar (400" WG) | MB7-DR-01-ST |
|