Roxspur Measurement and Control: For Good Measure RM&C LtdPlaton, Brearley, CT, Nulectrohms, SensitPhone 0870 22 00 724 or email sales@roxspur.com

For true average temperature measurement across large ducts up to 100°C.

  • Pt100 Sensing Element
  • Optional 4-20mA Output Signal
  • High Accuracy
  • True Average Reading
  • Flexible Probe
  • Compatible with Most Major B.E.M.S
Specification
Temperature-20 to 100C
Sensing Element100 ohms @ 0°C
Stem1/4" diameter copper brazed into 5/16” diameter 316 stainless steel extension.
HeadHigh impact ABS, protection class IP67 with duct mounting slots
WiringTwo-part terminals accepting up to 3.5mm 2 wires
Ambient Temperature-20 to 70°C (at the head)
AccuracyTo BS 1904 : 1984 / DIN 43760
Cable EntryM20 x 1.5mm threaded entry complete with nylon gland for cable diameters from 4.0mm to 7.0mm.