Roxspur Measurement and Control: For Good Measure RM&C Ltd

The GEN 1500 Series are DIN rail mounted transmitters designed to accept thermocouple or Pt100 temperature sensors and to isolate and convert them to the industry standard 4-20mA transmission signal. Automatic cold junction compensation is provided for thermocouples, whilst high accuracy is achieved with Pt100 sensors by using an active three or four wire bridge arrangement which effectively removes any errors associated with the sensor connecting cables.

Units are supplied pre-set for sensor type and temperature range required from the table or can easily be re-ranged by the customer using the Zero and Span potentiometers on the front panel.

Specification
Temperature-30 to 1600C
SensorPt100 to BSEN60751 - 2, 3 or 4 wire
Accuracy±0.15°C plus ±0.1% rdg. from 0 to 200°C, else ±0.15°C plus ±0.2% rdg.
Excitation2mA max. (2/3 wire), 1mA max. (2/4 wire)
SensorT/C types J, K, N, R, S or T
Accuracy±0.1% FRO plus cold junction errors
Cold JunctionAccuracy ±0.2°C @ 20°C, Tracking ±0.05°C/°C
Isolation500VDC (Flash tested to 1KV)
Burn OutUP scale
Output4-20mA loop powered, 30mA max
Loop Supply10 to 30VDC
Loop Resistance700 ohms max. @24V
Ambient Temp0 to 50°C
Ambient Humidity10 to 95%RH, non-condensing
Mounting"Top Hat" rail to DIN EN 50022-35