Products > Temperature > Temperature Measurement > Temperature Signal Conditioning > SMART DIN Rail Mount Temperature Transmitters
The GEN 220/230 Smart Din Rail Transmitters provide a current output from any of the common industrial sensors. All versions feature galvanic isolation from the power supply and input to output isolation.
The GEN 220/230 are microprocessor based and feature automatic self calibration of span and zero which results in excellent short and long term accuracy and repeatability. Linearisation is performed digitally to ensure drift free performance.
The GEN 230 offers all the features of the GEN 220 plus the following: |  |
- Additional Level of Input Isolation
- RS 485 Multi-Drop Communications
- Automatic or Programmable Cold Junction
- Non-Linear Inputs (÷ , Power 3/2, Power 5/2)
- User Defined Linearisation
- I.S. Approval
- Internal Tx Supply
- Alarm Relays Option
- Output Test Connector
- Intelligent Software Filter
- Peak & Valley Capture/Hold
- Watchdog Relay Option
- Programmable Safety Condition
Dual trip relays can be fitted on GEN 230 as an option. These are two individual relays with a common connection and each may be configured independently as high, low or deviation alarms. An additional feature enables the relays to be used for system healthy alarms. Each relay has an associated LED which is illuminated to show the alarm state.
The GEN 230 is available for hazardous area use. Although the units need to be mounted in a safe area, they have an isolated and intrinsically safe ‘front end’ which means that sensors can be connected directly in to the Hazardous area WITHOUT BARRIERS |
| Specification |
| Temperature | -270 to 1800C |
| Input/Output | 500 VAC |
| PSU | 2500 VAC |
| Power Supply | Option 1: 90-253VAC 50/60Hz
Option 2: 22-28VAC 50/60Hz 15-30VDC
Option 3: 90-130VAC 50/60Hz 20-100VDC |
| Power | GEN 220 4.5W max., GEN 230 6W max |
| Ambient Temp | 0 to 50°C, 0 to 40°C (I.S. Version) |
| Cold Junction | Accuracy ±0.2°C @ 20°C, Tracking ±0.05°C/°C |
| Storage Temp | -50 to 80°C |
| Case Size | 145 x 125 x 140mm |
| Mounting | Universal DIN rail foot |
| Output | 0/4-20mA (active or passive) |
| Loop Resistance | 1000W max |
| Sensor Specification |
| Sensor | Accuracy | Resolution | Nominal Range |
| K T/C | ±1.0°C | ±0.1°C | -270 to 1200°c |
| J T/C | ±1.0°C | ±0.1°C | -210 to 760°c |
| T T/C | ±1.0°C | ±0.1°C | -270 to 400°C |
| R T/C | ±2.0°C | ±0.5°C | 0 to 1750°C |
| S T/C | ±2.0°C | ±0.5°C | 0 to 1750°C |
| E T/C | ±1.0°C | ±0.5°C | 0 to 650°C |
| F(L) T/C | ±1.0°C | ±0.5°C | 0 to 600°C |
| N T/C | ±1.0°C | ±0.5°C | 0 to 1300°C |
| B T/C | ±3.0°C | ±0.5°C | 1000 to 1800°C |
| Cold Junction | ±0.5°C | ±0.1°C | 0 to 50°C |
| Pt100 | ±0.1°C, ±0.1% rdg | ±0.02°C | -200 to 800°C |
| Voltage |
| 10v | 0.02% FS | 0.004% | -10 to 10v |
| 5v | 0.04% FS | 0.008% | -5 to 5 v |
| 1-5v | 0.04% FS | 0.008% | 1 to 5 v |
| 1v | 0.02% FS | 0.004% | ±1v |
| 500mv | 0.04% FS | 0.008% | ±0.5v |
| 100mv | 0.02% FS | 0.004% | ±0.1v |
| 50mv | 0.02% FS | 0.004% | ±0.05v |
| Current |
| 4-20mA | 0.1% FS | 0.004% | 4-20mA |
| 0-20mA | 0.1% FS | 0.004% | 0-20mA |
| 0-10mA | 0.2% FS | 0.008% | 0-10mA |
| Slidewire | 0.1% FS | 0.004% | 1K to 50KOhm |
|