The GEN 210 is a second generation ‘Smart’ in head temperature transmitter that accepts any commonly used temperature sensor, slide-wire transducer or Millivolt signal and converts the output to the industry standard 4-20mA transmission signal.

The sensor type and range are easily programmed using a software package running under ‘WindowsTM’ on a PC which communicates, via an interface adapter, down the same pair of wires that carry the 4-20mA output signal.

The Process Variable may be filtered to remove incoming signal noise using one of the four settings. If the ‘Adaptive ‘ function is selected the filter continuously adjusts to the incoming signal to noise ratio in order to choose an appropriate level of filtering. In this way a slowly changing input can be heavily filtered but if the signal goes through a sudden change the filter quickly reduces allowing a rapid response.

Specification
SensorPt100 to BSEN6075
Sensor Range-200 to 850°C
Minimum Span25°C
LinearisationBSEN60751/BS1904/DIN 43760/JISC 1604
Accuracy± 0.01% Full Range Input, ± 0.05% Rdg
Excitation Current300mA to 550mA
Maximum Lead Resistance50 ohms/leg
Thermocouple TypeTC type K: -200 to 1370
TC type J: -200 to 1200
TC type T: -210 to 400
TC type R: -10 to 1760
TC type S: -10 to 1760
TC type E: -200 to 1000
TC type F (L): -100 to 600
TC type N: -180 to 1300
SensorT/C
Accuracy±0.04% FRI ±0.04% Rdg or 0.5°C (whichever is greater)
Cold Junction Error±0.5°C
Cold Junction Tracking0.05°C/°C
Cold Junctione-40 to 85°C
InputVoltage Source
Range-10 to +75mV
CharacterisationLinear
Minimum Span5mV
Accuracy±10mV plus ±0.07% rdg
Sensor3 wire potentiometer (slidewire)
Resistance Range10 ohms to 390 ohms (End to End)
CharacterisationLinear
Minimum Span5%
Accuracy0.1%
Output4-20mA loop powered, max. 25mA
Loop Supply10 to 35V polarity protected
Loop Resistance700 ohms max. @ 24V
Input/Output Isolation500 V AC rms
Filter FactorProgrammable Off, 2 seconds, 10 seconds or Adaptive
Ambient Operating Temp-40 to 85°C
Ambient Storage Temp-50 to 100°C
Configurable ParametersSensor type, Burnout, °C / °F, Output Hi/Lo, Filter, Tag, User Offset